UNI-T UT522 Earth Resistance Tester 4000Ω CAT III 600V

Product information "UNI-T UT522 Earth Resistance Tester 4000Ω CAT III 600V"

Main Product Features

  • Earth resistance measurement ranges: 0 to 40Ω, 0 to 400Ω, and 0 to 4000Ω
  • AC earth voltage measurement from 0 to 400V (50Hz/60Hz)
  • Measurement modes: Simple 2-wire testing and precise 3-wire testing
  • Safety category rating: CAT III 600V with double insulation protection
  • Digital LCD with 4000 display counts, backlight, and full icon display
  • Internal data storage for up to 20 measurement values
  • Operational alerts: Over-range display ('OL') and poor contact indication ('...Ω')
  • Automatic power off function and low battery indication

Ground Resistance and AC Ground Voltage Verification

The UNI-T UT522 enables electrical contractors and service technicians to test grounding installations across power distribution networks, industrial facilities, and lightning protection systems. Ground resistance can be assessed across three manual ranges up to 40 Ω, 400 Ω, and 4000 Ω. Furthermore, the unit evaluates AC ground voltages from 0 to 400 V at 50 Hz or 60 Hz.

Dual Testing Procedures and Connection Monitoring

For versatile field operations, the instrument supports simplified 2-wire testing as well as precise 3-wire earth resistance measurements using auxiliary earth spikes. The device actively monitors lead connectivity during the procedure: an inadequate connection triggers the on-screen alert ...Ω, whereas input signals exceeding the active range are signaled by OL.

Data Handling and Operating Features

Test results appear on an illuminated 70.6 x 34 mm LCD with 4000 display counts and comprehensive icon indicators. Technicians can retain figures using the data hold function or archive up to 20 individual readings inside the onboard memory. Built with double insulation to meet CAT III 600 V specifications, the portable instrument also features an automatic shut-off function to preserve the six AA cells during site visits.

Earth Resistance Ranges0–40Ω / 0–400Ω / 0–4000Ω
Earth Resistance Accuracy0–40Ω: ±(2%+20), 0–400Ω: ±(2%+3), 0–4000Ω: ±(2%+3)
AC Earth Voltage Range0–400V (50Hz/60Hz)
AC Earth Voltage Accuracy±(1%+6)
Display Count4000
Data Storage20 readings
Measurement CategoryCAT III 600V
InsulationDouble insulation protection
Power Supply6x 1.5V battery (LR6 / AA)
Display Dimensions70.6 x 34 mm
Dimensions (W x H x D)160 x 100 x 70.5 mm
Net Weight560 g

FAQ

What measurement methods does the UNI-T UT522 support?

The UT522 supports both simple 2-wire testing and precise 3-wire earth resistance testing.

What does the tester indicate if a contact problem occurs?

When there is poor contact during measurement, the display shows '...Ω'.

How many measurement records can be stored directly on the device?

The internal memory of the UT522 can store up to 20 measurement values.

What is the measurement category of the UT522?

The instrument is specified with a safety rating of CAT III 600V and features double insulation protection.

Technical data
Product number: 202659

Manufacturer

Company Name
Uni-Trend Technology (China) Co., Ltd.

Address
No.6, Gong Ye Bei 1st Road, Songshan Lake National High-Tech Industrial Development Zone,
Dongguan City, Guangdong Province, 523 808, CN

Phone
(+86-769)85723888

EU Responsible Person

Company Name
P+C Schwick GmbH

Address
Bergisch Born 87A, 42897 Remscheid, NRW, Germany

E-Mail
info@schwick.de

Phone
+492191598280